OPC Collector Sample Interval doesn't seem to work

I changed the Sample Interval within the OPC Collector session group to be 1 minute, but when I look at the data in the historian, it still appears to be logging every value change?

 

1reply Oldest first
  • Oldest first
  • Newest first
  • Active threads
  • Popular
  • Hi Big_Bird

    It's possible that the OPC UA server does not support the interval you wish to use. If you look in the message log, you may find this warning:  

    Essentially, we suggest to the OPC server for an interval we want to use, but the OPC server replies back with a revised interval because the interval you want to use is not supported (or possibly needs configured within the OPC server). In this case, it used 00:00:00 instead of 1 minute.

    Like